Proximity Sensors # E2E-X2ME1-Z "Omron"
รายละเอียด
Cylinder type sensing head size | M8 |
---|---|
Type | Unshielded |
Sensing method | Inductive type |
Sensing distance | 2 mm -10% to +10% |
Setting distance | 0 to 1.6 mm |
Differential distance | 10% Max. of sensing distance |
Sensing object | Ferrous metal (Sensitivity lowers with non-ferrous metals.) |
Standard sensing object | Iron 12*12*1mm |
Response frequency | 0.8 kHz (average) |
Power supply voltage | 12 to 24 VDC (ripple(p-p) :10% Max.) |
Operating voltage range | 10 to 40 VDC |
Current consumption | 13 mA Max. |
Control output (Output type) | NPN voltage-current output |
Control output (Switching capacity) | 0 to 200 mA |
Control output (Residual voltage) | 2 V Max. (under load current with cable length of 2m) |
Indicator | Operation indicator(red) |
Operation mode | NO |
Protective circuit | Surge suppressor Output short-cut protection Power supply reverse polarity protection |
Standard or Different frequency | Standard |
Ambient temperature | Operating: -40 to 85 CEL Storage: -40 to 85 CEL (with no icing or condensation) |
Ambient humidity | Operating: 35 to 95 %RH Storage: 35 to 95 %RH (with no condensation) |
Temperature influence | +-10% Max. of sensing distance in temperature range of -25 to +70CEL +-15% Max. of sensing distance in temperature range of -40 to +85CEL (As the basis for sensing distance of 23CEL) |
Voltage influence | +-1% Max. of sensing distance in rated voltage range +-15%. (As the basis for sensing distance at standard power voltage) |
Insulation resistance | 50 M OHM Min. at 500VDC between charged parts and the case |
Dielectric strength | 1000 VAC 50/60 Hz for 1 minute between charged parts and the case |
Vibration resistance | 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions |
Shock resistance | 500m/s2 for 10 times each in X, Y, and Z directions |
Degree of protection | IEC60529: IP67 Company standard: Oil-proof |
Applicable standard (EC Directive (Low Voltage Directive)) | EN60947-1 EN60947-5-2 |
Applicable standard (EC Directive (EMC Directive)) | EMI: EN60947-5-2 Emission Enclosure: CISPR11 Group 1 class A EMS: EN60947-5-2 Immunity ESD: IEC61000-4-2 Immunity RF-interference: IEC61000-4-3 Immunity Conducted Disturbance: IEC61000-4-6 Immunity Burst: IEC61000-4-4 CE marking: Equipped |
Applicable standard (CCC mark) | Not equipped |
Connection method | Pre-wired models (Cable length: 2 m) |
Weight (Packed state) | approx. 65 g |
Material (case) | Stainless steel (SUS303) |
Material (sensing surface) | PBT |
Material (clamping nuts) | Brass nickel plating |
Material (toothed washer) | Iron zinc plating |
Accessories | Instruction manual |